May 2018 Archives
Thu May 10 13:44:16 +07 2018
Battery replacement
How to replace the battery in the UPS at CSIM.
EPC powercom 2kVA
Battery: 6x12V 9Ah Last replacement: May 2018
1. | Pull on the middle front bezel, then slide it to the right to un-hook it. | ||
2. | Remove the screw then slide the retaining bar to the left. | ||
3. | Pull on the battery drawer. | ||
4. | Follow the diagram to install the new bateries: two sets of 3 batteries in serie |
APC Smart UPS 3000XL
Power: 3kVA
Battery: 4x12V 18Ah
Last replacement: May 2018
1. | Remove the front bezel, then remove both screws to open the battery compartment. | ||
2. | Follow the diagram to install the new bateries: two sets of 2 batteries in serie |
APC Smart UPS 5000
Power: 5kVA
Battery: 16x12V 9Ah
Last replacement: May 2018
1. | Remove the front bezel, then remove both screws to open the battery compartment. | ||
2. | Pull on the cord to disconnect the battery set, then use the tab to extract the battery set. | ||
3. | Follow the diagram to install the new bateries: four sets of 4 batteries in serie¶llel (2+2) |